Refrigeration System Maintenance and Troubleshooting Guide

The refrigeration system is a general term for the equipment and pipelines through which the refrigerant flows, including compressors, condensers, throttling devices, evaporators, pipelines and auxiliary equipment. It is the main component system of air conditioning equipment, cooling and refrigeration equipment.

The blockage failure of the refrigeration system has many forms such as ice blockage, dirty blockage and oil blockage. The unified fault characteristics of blockage are: the condenser is not hot when touched, the evaporator is not cold, the compressor operating current is smaller than normal, the pressure gauge is connected to the bypass charging valve, indicating negative pressure, the outdoor unit is running light, and there is no sound of liquid in the evaporator.

448247525_122161720502202379_3994650262628731810_nCauses and fault phenomena of ice blockage

The occurrence of ice blockage failure is mainly due to excessive moisture in the refrigeration system. With the continuous circulation of refrigerant, the moisture in the refrigeration system gradually concentrates at the capillary outlet. Since the temperature at the capillary outlet is the lowest, the water freezes into ice and gradually increases. To a certain extent, the capillary is completely blocked, the refrigerant cannot circulate, and the refrigerator does not refrigerate.

The main source of moisture in the refrigeration system is: the motor insulation paper in the compressor contains moisture, which is the main source of moisture in the system. In addition, the components and connecting pipes of the refrigeration system have residual moisture due to insufficient drying; the refrigeration oil and refrigerant contain more moisture than the allowable amount; during the assembly or maintenance process, the pipeline is in an open state for a long time, causing the moisture in the air to be absorbed by the motor insulation paper and refrigeration oil. Due to the above reasons, the water content of the refrigeration system exceeds the allowable amount of the refrigeration system, resulting in ice blockage. On the one hand, ice blockage causes the refrigerant to be unable to circulate and the refrigerator cannot refrigerate normally; on the other hand, moisture will also react chemically with the refrigerant to generate hydrochloric acid and hydrogen fluoride, causing corrosion to metal pipes and components, and even causing insulation damage to the motor windings. At the same time, it will also cause the refrigeration oil to deteriorate and affect the lubrication of the compressor. Therefore, the moisture in the system must be controlled to a minimum.

The manifestation of ice blockage in the refrigeration system is that it works normally in the initial stage, frost in the evaporator, heat dissipation in the condenser, stable operation of the unit, and clear and stable sound of refrigerant activity in the evaporator. As ice blockage forms, the airflow can be heard to gradually weaken and intermittently. When the blockage is serious, the airflow sound disappears, the refrigerant circulation is interrupted, and the condenser gradually cools down. Due to the blockage, the exhaust pressure increases, the machine running sound increases, no refrigerant flows into the evaporator, the frosting area gradually decreases, the temperature gradually increases, and the capillary temperature also rises, so the ice begins to melt, and the refrigerant begins to circulate again. After a period of time, ice blockage occurs again, forming a periodic pass-blocking phenomenon.WechatIMG3155

Causes and failure phenomena of dirty blockage

The formation of dirty blockage failure is caused by excessive impurities in the refrigeration system. The sources of impurities in the system are mainly: dust and metal chips in the refrigerator manufacturing process, the oxide layer of the inner wall falls off during pipe welding, the inner and outer surfaces of each component are not cleaned during the processing process, the pipeline is not tightly sealed and dust enters the pipe, the refrigeration oil and refrigerant contain impurities, and the poor quality desiccant powder in the dry filter. Most of these impurities and powders are removed by the filter drier when they flow through it. When there are more impurities in the filter drier, some fine dirt and impurities are brought into the capillary by the refrigerant with a higher flow rate, and are retained and accumulated in the capillary bend with greater resistance. The resistance is getting bigger and bigger, making it easier for impurities to be retained until the capillary is blocked and the refrigeration system cannot circulate. In addition, the close distance between the capillary and the filter in the filter drier can also easily cause dirty blockage failure; in addition, it is also easy to weld the capillary tube mouth when welding the capillary and the filter drier.

After the refrigeration system is dirty and blocked, the refrigerant cannot circulate, so the compressor runs continuously, the evaporator is not cold, the condenser is not hot, the compressor shell is not hot, and there is no airflow sound in the evaporator. If it is partially blocked, the evaporator feels cool or cold, but no frost. When touching the outer surface of the filter drier and the capillary, it feels very cold, there is frost, and even a layer of white frost. This is because when the refrigerant flows through a slightly blocked filter drier or capillary, a throttling and pressure reduction effect is generated, causing the refrigerant flowing through the blockage to expand, vaporize, and absorb heat, resulting in condensation or frost on the outer surface of the blockage.

The difference between ice blockage and dirty blockage: ice blockage can restore refrigeration after a period of time, forming a period of smoothness and blockage, blocking and smoothness, smoothness and blockage. However, after dirty blockage occurs, refrigeration cannot be achieved.

In addition to dirty blockage of the capillary, if there are too many impurities in the system, the filter drier will gradually be blocked. Because the filter itself has a limited capacity to filter out dirt and impurities, it will be blocked due to the continuous accumulation of impurities.f5b0af95a64da74643efc29731660e32

Oil blockage and other pipeline blockages

The main reason for oil blockage in the refrigeration system is that the compressor cylinder is severely worn or the clearance between the piston and the cylinder is too large.

The gasoline discharged from the compressor is discharged into the condenser, and then enters the filter drier together with the refrigerant. Due to the high viscosity of the oil, it is blocked by the desiccant in the filter. When there is too much oil, it forms a blockage at the filter inlet, so that the refrigerant cannot circulate normally and the refrigerator does not refrigerate.

The reasons for the blockage of other pipelines are: the pipeline is blocked by solder during welding; or the replaced pipe is blocked without being discovered when the pipe is replaced. The above blockages are caused by human factors. Therefore, it is required to operate and check as required when welding and replacing pipes, so as not to cause human blockage failure.cb8065380cd79123d51383e3ab345982b3b780b1

Methods for eliminating blockage of refrigeration system

Elimination of ice blockage

Ice blockage failure occurs in the refrigeration system because there is excessive moisture in the system, so the entire refrigeration system must be dried. There are two ways to deal with it:

1. Use a drying box to heat and dry each component. Remove the compressor, condenser, evaporator, capillary tube, and return air pipe in the refrigerant system from the refrigerator, put them in the drying box for heating and drying. The temperature in the box is about 120℃, and the drying time is 4 hours. After natural cooling, use nitrogen to blow and dry them one by one. Replace the new drying filter, and then assemble and weld, pressurize and detect leaks, evacuate, fill with refrigerant, test run and seal. This method is the best way to eliminate ice blockage, but it is only suitable for the warranty department of the refrigerator manufacturer. Generally, repair departments can use heating and vacuuming methods to eliminate ice blockage faults.

2. Use heating vacuuming and secondary vacuuming methods to eliminate moisture from various components of the refrigeration system.

图2Elimination of dirty blockage faults

There are two ways to eliminate the capillary blockage fault: one is to use high-pressure nitrogen combined with other methods to blow out the dirt in the blocked capillary. After the capillary is blown through, the various components in the refrigeration system are cleaned and dried, and then reassembled and welded to eliminate the fault. If the capillary is seriously blocked and the above methods cannot eliminate the fault, the method of replacing the capillary is used to eliminate the fault, which is described as follows:

1. Use high-pressure nitrogen to blow out the dirt in the capillary: cut the process pipe to drain the liquid, weld the capillary off the drying filter, connect the three-way repair valve to the compressor process pipe, fill it with 0.6~0.8MPa high-pressure nitrogen, and straighten the capillary to heat it with a gas welding carburizing flame to carbonize the dirt in the pipe, and blow out the dirt in the capillary under the action of high-pressure nitrogen. After the capillary is unblocked, add 100 ml of carbon tetrachloride for aeration and cleaning. The condenser can be cleaned with carbon tetrachloride on the pipeline cleaning device. Then replace the dry filter, fill with nitrogen for leak detection, evacuate, and finally fill with refrigerant.

2. Replace the capillary: If the dirt in the capillary cannot be flushed out by the above method, the capillary can be replaced together with the low-pressure pipe. First, use gas welding to remove the low-pressure pipe and the capillary from the copper-aluminum joint of the evaporator. When disassembling and welding, the copper-aluminum joint should be wrapped with wet cotton yarn to prevent the aluminum tube from being burned by high temperature.

When replacing the capillary, the flow rate should be measured. The capillary outlet is not welded to the evaporator inlet first. The repair valve and pressure gauge are installed at the suction and exhaust inlet and outlet of the compressor respectively. After the compressor is running, air is sucked from the low-pressure repair valve. When the suction pressure is equal to the external atmospheric pressure, the indicated pressure of the high-pressure gauge should be stable at 1-1.2MPa. If the pressure exceeds, it means that the flow rate is too small. A section of the capillary can be cut off until the pressure is appropriate. If the pressure is too low, it means that the flow rate is too large. You can coil the capillary several times to increase the resistance of the capillary, or replace a capillary. After the pressure is appropriate, weld the capillary to the inlet pipe of the evaporator.

When welding a new capillary, the length inserted into the copper-aluminum joint should be about 4 to 5 cm to avoid welding blockage. When welding the capillary to the dry filter, the insertion length should be 2.5 cm. If the capillary is inserted too much into the dry filter and too close to the filter, tiny molecular sieve particles will enter the capillary and block it. If the capillary is inserted too little, impurities and molecular sieve particles during welding will enter the capillary and directly block the capillary channel. Therefore, the capillary should not be inserted too much or too little into the filter. Too much or too little will cause the risk of blockage. Figure 6-11 shows the connection position of the capillary and the dry filter.

432549266_122133897482102829_6978136061424866934_nTroubleshooting of oil blockage

Oil blockage indicates that there is too much refrigeration oil remaining in the refrigeration system, which affects the refrigeration effect or even fails to refrigerate. Therefore, the refrigeration oil in the system must be cleaned up.

When the filter is clogged with oil, a new filter should be replaced. At the same time, high-pressure nitrogen should be used to blow out some of the refrigeration oil accumulated in the condenser. When nitrogen is introduced, a hair dryer can be used to heat the condenser.

 

 

TAGS:

Contacts & Support

Focusun Refrigeration Corporation
Room 603, Baohong Center
No. 7755 Zhongchun Rd
Shanghai CHINA
ZipCode: 201100

Tel: +86-21-5108 9946
Fax: +86-21-5227 2259
Email: enquiry@focusun.com

Sales: sales@focusun.com
Marketing: marketing@focusun.com
Press: press@focusun.com

Newsletter: newsletter@focusun.com
WhatsApp